Basic Superelevation Rules of Thumb
1. Always have report lock turned on when working with
superelevation. This produces a report that includes lots of
useful data.
2. Non-Linear transitions require 1-1/2 greater
transition length than linear transitions do for the same rate of
change. Kentucky uses linear transition as the Inside and Outside
Transition Mode.
3. The Tangent Point:
parameter is used only when a spiral is present in the
transition. If Normal Crown is selected all the
transition; both runoff and runout, occurs on the spiral,
spilling on to a portion of the curve if necessary. If Zero
Slope is selected the tangent to spiral station
will separate the superelevation runoff from the tangent runout.
4. Delta G is the rate of superelevation transition
expressed as a percentage. Strictly, Delta G is the distance that
the range point of the template rises during a given transition
divided by the length of the transition. A 1:200 rate of change
for 50 mph design would equate to a Delta G of 0.5.
Table Method
1. The `Deg Crv' column for the degree of curvature is completely
ignored, so changing it has no effect whatsoever. Radius values
less than or equal to the exact degree of curvature radius should
be used in the tables. Do not round degree of curvature radius
lengths up. Superelevation tables must begin with the longest
radii, then decrease in length down the page.
2. There is a 40 entry limit to superelevation tables. There must
be a `NC' entry in the table or the first super rate will
be applied to curves with radius longer than the first entry;
even though they may not require superelevation. Curves with
radii that fall between the `NC' entry and the first super
rate will have the first super rate applied.
3. Super rates are interpolated from the `Super Rate' column in
the specified table based on radii except as noted above. Any
curve tighter than the shortest radii gets the maximum rate.
4. Runoff lengths are not interpolated from neither the
2-lane nor the 4-lane transition length columns of a specified
table. The table runoff length used will be the value associated
with the table radius that is either equal to or less than the
actual alignment radius.
5. Superelevation from the table method invokes some special
circumstances in the `tangent point' parameters referred
to above in Basic Superelevation Rules of Thumb. Refer to
the left side of the Superelevation Runoff Flow Chart for
clarification.
6. The superelevation tables delivered with InRoads yield results
very close to superelevation calculated based on AASHTO method 5.
Templates
1. Correct superelevation on typical sections with curb and
gutter can be achieved utilizing Rollover Locks. Imagine a
4 lane template that has 24' of pavement at 1/4 " per foot;
2.08%, and a 2' gutter that slopes at 1" per foot; 8.33%
(curb and gutter has 30" width over all). The super
elevation range is typically defined from gutter to gutter, so
your super elevating 26' of travel-way on each side of the
centerline. If the maximum super rate is set at something less
than the gutter slope the low side gutter slope will stay at
8.33%. In InRoads, the super rate is based on the total vertical
difference in the super range divided by the total horizontal
distance defined in the super range, not the individual
components. Assume e-max is 6.00%, and a curve warrants full
super. The 24' pavement section on the low side of the curve will
never attain full super; 6.00%, it will only be 5.8% because the
gutter section is held at the defined value of 8.33%. To achieve
the desired results the super range should be set at the lip of
the curb instead of in the gutter. The trick to getting the high
side gutter to spill is to use rollover locks set at 0%
difference on only the outside portion of the curve.
Utilizing this method the low side gutter will retain its proper
slope, but the high side gutter will spill.
Superelevation Workflow for Kentucky Transportation Cabinet
1. Layout proposed horizontal and vertical alignments. Horizontal
spiral lengths based on AASHTO minimum length runoff values.
2. Having created a superelevation definition in the active
geometry file, create and define the Template Library and the
Roadway Library.
3. From the
Superelevation palette select Superelevation Rate
Calculator. Under Settings select Rate Parameters.
In the Superelevation Rate Calculator Parameters dialog
box set the Rate Calculation Method: to Table Method, set
the Rate Table Name: to the desired super table, the Column
from Rate Table to either 2-lane or 4-lane as appropriate.
The Round Rates to: option may be toggled on at this
point. The Desirable Max Super Rate: will warn the
designer if a preferred e-max is exceeded. The desirable max
super rate may be less than the absolute max super rate. Setting
the desirable max super rate equal to the absolute max super rate
will result in no warning messages.
Upon completion of setting the desired parameters select
the Close button. Press the OK button in the Superelevation
Rate Calculator dialog box. The Review / Edit
Superelevation Rates dialog box will appear on the screen
displaying the calculated superelevation rates. The calculated
superelevation
rates can either be accepted by pressing the OK
button, or edited by selecting the Edit button. Upon
completion of editing select the OK button.
4. From the
Superelevation palette select Build Application
Stations. Verify the active Horizontal Alignment and revise
as necessary the Vertical Alignment, Active SuperAlignment and
Roadway Definition. Under Settings select Default
Params. The Superelevation Default Parameters dialog
box will activate. Set the Inside Transition Mode: and the
Outside Transition Mode: as desired. Make certain the Tangent
Point: is Zero Slope and Maximum Delta G is
toggled off. Zero Slope will ensure that the runoff is on
the spiral. If Maximum Delta G is toggled on it could override
the Tangent Point-Zero Slope control based upon the
computed transition length. If Maximum Delta G is used and
the computed runoff exceeds the spiral length, the runoff will
begin on the tangent-spiral station. The %Runoff on Tangent:,
Minimum Tangent Length: and Minimum Runoff Length: settings
have no affect on the superelevation application station
calculations in this configuration.
If rollover locks are to be used,
select the Locks option in the Superelevation Default
Parameters dialog box. The Shoulder Rollover Locks
dialog box will activate. Configure the shoulder rollover locks
in accordance with the proposed design, then select OK to
accept the settings and dismiss the Shoulder Rollover Locks
dialog box. The Superelevation Default Parameters dialog
box will once again become active, select OK to accept the
settings and dismiss the Superelevation Default Parameters
dialog box. Press Apply in the Build Application
Stations to initiate the superelevation application station
calculations.
If there are no problems
with the superelevation ranges the Build / Edit Application
Stations dialog box will activate. If a superelevation range
overlap occurs an Information dialog box will activate to
notify the designer. Select OK in the Information
dialog box and the Build / Edit Application Stations
dialog box will activate. Overlaps may be resolved by either
editing the application stations in the Build / Edit
Application Stations dialog box, or by recompiling the
superelevation based on a different e-max value and/or spiral
length.
If the report lock is toggled on a Superelevation
Application Station Calculations report will activate. This
report is the easiest way to see how the super is being applied.
If revisions to the superelevation transition lengths are deemed
appropriate then the spiral lengths on the horizontal curves
should be revised. All of the settings will be maintained within
InRoads; you may want to save the preferences to reload and use
on other projects, so only the basic steps to compute the
superelevation must be repeated.
|